RAMCRO – BMS-PVC-BC-Screened Cable
& Free Shipping
Brand Name: | RAMCRO |
Part Number: | R1007 |
Product Type: | RAMCRO – BMS-PVC-BC-Screened Cable |
Specification: | Please refer to the Datasheet on the Manufacturer’s Datasheet |
Warranty: | Manufacturer Standard Warranty |
- Applicable on : Orders above Rs. 500.
- Bank offer : 5% Cashback on paypal card.
- Coupon code : Use code "FLIPMART10OFF".
- Delivered : Usually delivered in 6 days.
RAMCRO – BMS-PVC-BC-Screened Cable
Details:
RAMCRO – BMS-PVC-BC-Screened Cable
Specifications:
Multicore, PP-Insulation, Collective Screened, PVC-Sheath
Application
PVC sheathed multi-conductor cables are suitable for Building Management Systems (BMS), Sound, Audio, Security, Safety, Control and Instrumentation.
Construction
Formation: 2 Cores
Section: 16 AWG
Conductor: Plain annealed copper wire, Multistrand
Insulation: Polypropylene – PP
Colour Code: Colour Code
Individual Screen: N.A.
Wrapping: at least 1 layer of plastic tape 0,023 mm
Collective Screen: 0,026 mm Aluminium / PETP tape over tinned copper drain wire
Inner Sheath: N.A.
Armour: N.A.
Outer Sheath: Polyvinyl chloride – PVC – Grey RAL 7001
Cable Printing: SCREENED PVC 300 V 75 C IEC 60332-1/UL 1581 – SAS0203HBAXH-RB – “PROD.WEEK/18” + BATCH + METER MARKING
Technical Data & Standard References
Fire Propagation:
- Test on single cable – IEC 60332-1
- Test on bunched cables – IEC 60332-3
- Limiting Oxygen Index (LOI) – (min 30%)
- Smoke Density – IEC 61034
- Amount of halogen acid gas – IEC 60754-1 (max 15%)
- Acidity (ph value) and conductivity – IEC 60754-2
- Sunlight resistance – UL 1581 section 1200
Electrical & Mechanical Data
- Conductor Cross-section Temperature Range – Nom – 16 AWG
- DC Resistance per core at 20° C -30°C up to 80°C – max Ω/km – 15,47
- Insulation Resistance at 20° C – min MΩ*km – 1000
- Nominal Mutual Capacitance – max pF/m – 105
- Inductance 8 x cable diameter – V – 2000
- Test Voltage – Core/Screen 40 – V – 2000
- Operating Voltage – V – 300
Temperature Range:
- During Operation – ° C – -30°C up to 80°C
- During Installation – ° C – -30°C up to 80°C
- Bending Radius – mm – Inductance 8 x cable diameter
- Max Pulling Tension – N/mm2 – 116
- Weight Approx – kg/km – 40
- Put up length – mt – 305